Operating features
Rated voltage Uo/U is 450/750V(600/1000V).
Allowed continuous working temperature of conductor is 90℃
Installation temperature of cables should be no less than 0℃ . Bending radius should be not less than 12 times O.D. of cable.
Max. Temperature of conductor (Max. 5sec. duration) should be not more than 250℃ .
1. Application
The cables are designed for connection wires of power distribution equipment for controlling, monitoring, protecting circuits with A .C. rated voltage 450/750V (0.6/1kV)and below.
2. Standards
GB/T9330-2008 ,IEC 60502, etc.
*Ruitian can also design and produce for special application requirement.
category:Controlled Shielded Cable
3. Operating features
3.1 Rated voltage Uo/U is 450/750V(600/1000V).
3.2 Allowed continuous working temperature of conductor is 90℃
3.3 Installation temperature of cables should be no less than 0℃ . Bending radius should be not less than 12 times O.D. of cable.
3.4 Max. Temperature of conductor (Max. 5sec. duration) should be not more than 250℃ .
4. Type,description and main application Table
Chinese Type | Description | Main Application |
KYJV |
Copper conductor XLPE insulated and PVC sheathed control cable |
Laying indoors,in trenches, in ducts and directly in ground |
KYJVR |
Copper conductor XLPE insulated and PVC sheathed flexible control cable |
|
KYJVP |
Copper conductor XLPE insulated and PVC sheathed control cable with copper tape lapping screen |
Laying indoors,in trenches, in ducts directly in ground and other places that interference-resistance is requested. |
KYJVP2 |
Copper conductor XLPE insulated and PVC sheathed flexible control cable with braiding screen |
|
KYJVRP |
Copper conductor XLPE insulated and PVC sheathed control cable with copper tape longitudinal screen |
|
KYJVRP2 |
Copper conductor XLPE insulated and PVC sheathed flexible control cable with copper tape lapping screen |
|
KYJV22 |
Copper conductor XLPE insulated and PVC sheathed control cable with steel tape armour |
For flxed installation,laying indoors, in trenches and ducts,directly in ground where heavier mechanical force withstood |
KYJV32 |
Copper conductor XLPE insulated and PVC sheathed control cable with steel wire armour |
For laying indoor, in tunnels, ducts, conduit and direct burial etc. Permanent place, able to bear greater mechanical force |
KYJVP2-22 |
Copper conductor XLPE insulated and PVC sheathed steel tape armored control cable with copper tape lapping screen |
For fixed installation, laying indoors, in trenches and ducts,directly in ground where heavier mechanical force and interference resistance withstood |
NOTE: Ruitian can produce “Flame-Retardant Series”, “Fire-Resistant Series”, “Low Smoke Halogen Free (LSHF/LSOH) Series”,“Low Smoke Low Halogen (LSLH) Series”, etc. control cable as customer required.
Performance in line with IEC60332: 2004 requirements.
5. Production range
Type |
Rated voltage V |
Nom.area of conductor (m㎡) | ||||||
0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | ||
No.of cores | ||||||||
KYJV | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVR | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVRP | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVP | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVP2 | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVRP | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVRP2 | 450/750 | 2~61 | 2~61 | 2~61 | 2~14 | 2~14 | 2~14 | 2~10 |
KYJVPT | 450/750 | 2~61 | 2~61 | 2~61 | 4~14 | 4~14 | 4~14 | 4~10 |
KYJVPL | 450/750 | 7~61 | 7~61 | 4~61 | 4~14 | 4~14 | 4~14 | 4~10 |
KYJVP2-22(A) | 450/750 | 4~61 | 4~61 | 4~61 | 4~14 | 4~14 | 4~14 | 4~10 |
KYJVPT-22(A) | 450/750 | 4~61 | 4~61 | 4~61 | 4~14 | 4~14 | 4~14 | 4~10 |
KYJVPL-22(A) | 450/750 | 4~61 | 4~61 | 4~61 | 4~14 | 4~14 | 4~14 | 4~10 |
KYJV type 450/750V(0.6/1kV) copper conductor XLPE insulated and PVC sheathed control cable to GB/T9330-2008