Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
Rated voltage: 0.6/1(1.2)kV(Low Voltage Power Cable)
Max. permissible continuous operating temperature of conductor: 70°C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:
Nominal cross section of conductor ≤300mm2: 160°C
Nominal cross section of conductor >300mm2: 140°C
The ambient temperature under installation should not be lower than: 0°C
The bending radius of cable is recommended as following:
For single core cable: not less than 20 times of the diameter of cable
For multi-core cable: not less than 15 times of the diameter of cable
Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
Manufacturing Standards: GB/T 12706-2008, IEC 60502-1
Description
Type | Description | No. of cores | Nominal cross section of conductor |
VV |
Copper conductor PVC insulation PVC outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
VY |
Copper conductor PVC insulation PE outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
ZA-VV ZB-VV ZC-VV |
Copper conductor PVC insulation flame-retardant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~630mm² |
NH-VV |
Copper conductor PVC insulation fire-resistant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |