1. Cable conductor Max work temperature XLPE insulation 90℃.
2. Short circuit XLPE insulation cable conductor Max work temperature no more than 250°C,duration time no more than 5s.
3. When install the cable, the work temperature should not lower than 0°C.
4. The bending radius of cable is recommended as following:
Rated voltage: 0.6/1(1.2)kV(Low Voltage Power Cable)
1. Cable conductor Max work temperature XLPE insulation 90℃.
2. Short circuit XLPE insulation cable conductor Max work temperature no more than 250°C, duration time no more than 5s.
3. When install the cable, the work temperature should not lower than 0°C.
4.The bending radius of cable is recommended as following:
For single core cable: not less than 15 times of the diameter of cable
For multi-core cable: not less than 12 times of the diameter of cableA
When the armoured single core cable used for Alternative Current(AC) system, the armour material should be non-magnetic.
Description
Type | Description | No. of cores |
Nominal cross section of conductor |
YJV32 |
Copper conductor XLPE insulation Steel Wire Armoured PVC outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
YJV33 |
Copper conductor XLPE insulation Steel Wire Armoured PE outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
ZA-YJV32 ZB-YJV32 ZC-YJV32 |
Copper conductor XLPE insulation Steel Wire Armoured flame-retardant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
WDZA-YJY33 WDZB-YJY33 WDZC-YJY33 |
Copper conductor XLPE insulation Steel Wire Armoured Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
NH-YJV32 |
Copper conductor XLPE insulation Steel Wire Armoured fire-resistant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm² |
Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid in high fall area, able to bear external mechanical force, and certain pulling
Manufacturing Standards: GB/T 12706-2008, IEC 60502-1